EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE
4
QUICK INSTALLATION
The procedure below is intended for trained personell with previous experience in installing EDS
Beam Smoke Detectors RK90R. If you don’t have the needed experience please refer to the standard
installation procedure of this manual.
1 - Fix the RK90R detector
2 - Connect the cables
3 - Set the JP2-JP3-JP4-JP5-JP7 jumpers (see pag.10)
4 - Make the optical allignment with the lamp
5 - Set the JP7 jumper in accord with the detector/riflector distance (tab.pag.9)
6 - Set JP1 in ON position (Allignment) (pag.10)
7 - Optimize the device signal using:
• the P1 trimmer
•
the adjustment screws V1-V2-V3 on the optical block
• a multimeter (or the STS01 instrument)
• Blue/Red Led signal level indication (fig.8 board)
8 - with the P1 trimmer regulate the signal between 4,7V and 5V.
9 - Verify the operational obcuring the reflector
10 - select the desired sensibility of the Obscuration circuit with the SW2 selector (40-50-60-
70%)
11 - select the desired sensibility of the Turbulence (Heat) circuit with the SW1 selector (if used)
12 - set JP1 in the OFF position to activate the device
11 - close the cover within 5 minutes
12 - wait at least 5 minutes for the device to become operational
13 - perform operational tests